Таймеры Omron H3YN-B

Компактные многофункциональные таймеры для установки в монтажную колодку
- Доступна монтажная колодка с безвинтовыми клеммами типа «Push-in plus» (PYF-__-PU) — удобное подключение проводов.
- Простая замена — сокращение времени обслуживания системы.
- Компактный корпус шириной 15,5 мм — экономия места.
- Большой прозрачный диск — простая установка времени срабатывания.
Заказная информация
Operating modes | Control output | Supply voltage | Order code | |
---|---|---|---|---|
Short-time range (0.1 s to 10 min) | Long-time range (0.1 m to 10 h) | |||
On-delay, Interval, Flicker OFF-start, Flicker ON Start |
DPDT | 24 VAC | H3YN-2-B AC24 | H3YN-21-B AC24 |
24 VDC | H3YN-2-B DC24 | H3YN-21-B DC24 | ||
12 VDC | H3YN-2-B DC12 | H3YN-21-B DC12 | ||
100 to 120 VAC | H3YN-2-B AC100-120 | H3YN-21-B AC100-120 | ||
200 to 230 VAC | H3YN-2-B AC200-230 | H3YN-21-B AC200-230 | ||
4PDT | 24 VAC | H3YN-4-B AC24 | H3YN-41-B AC24 | |
24 VDC | H3YN-4-B DC24 | H3YN-41-B DC24 | ||
12 VDC | H3YN-4-B DC12 | H3YN-41-B DC12 | ||
100 to 120 VAC | H3YN-4-B AC100-120 | H3YN-41-B AC100-120 | ||
200 to 230 VAC | H3YN-4-B AC200-230 | H3YN-41-B AC200-230 | ||
4PDT, Twin Contact | 24 VDC | H3YN-4-Z-B DC24 | H3YN-41-Z-B DC24 |
Характеристики
Item | H3YN-2-B/H3YN-21-B | H3YN-4-B/H3YN-41-B/H3YN-41-Z-B |
---|---|---|
Time ranges | 0.1 s to 10 min (1 s, 10 s, 1 min, or 10 min max. selectable) | 0.1 min to 10 h (1 min, 10 min, 1 h, or 10 h max. selectable) |
Rated supply voltage | 24, 100 to 120, 200 to 230 VAC ( 50/60 Hz), 12, 24 VDC | |
Pin type | Plug-in | |
Operating mode | ON-delay, interval, flicker OFF-start, or flicker-ON start selectable by DIP switch | |
Operating voltage range | 85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage) | |
Reset voltage | 10% max. of rated supply voltage | |
Control outputs | DPDT: 5 A at 250 VAC, resistive load (cosφ = 1) The minimum applicable load is 1 mA at 5 VDC (P reference value). Contact materials: Ag 4PDT: 3 A at 250 VAC, resistive load (cosφ = 1) H3YN-4-B/-41-B series: The minimum applicable load is 1 mA at 1 VDC (P reference value) H3YN-4-Z/-41-Z-B series: The minimum applicable load is 1 mA at 1 VDC (P reference value) Contact materials: Au-clad + Ag-alloy |
|
Accuracy of operating time | ±1% FS max. (1 s range: ±1%±10 ms max.) | |
Setting error | ±10% ±50 ms FS max. | |
Reset time | Min. power-opening time: 0.1 s max. (including halfway reset) | |
Influence of voltage | ±2% FS max. | |
Influence of temperature | ±2% FS max. | |
Ambient temperature | Operating: −10°C to 55°C (with no icing) Storage: −25°C to 65°C (with no icing) |
|
Degree of protection | IP40 (Terminal screw sections are excluded.) | |
Size in mm (H x W x D) | 28 x 21.5 x 52.6 |