Корзина пуста
Автоматические выключатели Omron J7MN

Omron J7MN - автоматические выключатели защиты двигателя на токи от 0,1 до 100 A
Автоматы: | ||||
---|---|---|---|---|
Диапазон установок, A |
Для двигателя 3x400V, kW |
![]() |
![]() |
![]() |
0.11-16 0.14-0.2 0.18-0.25 0.22-0.32 0.28-0.4 0.35-0.5 0.45-0.63 0.55-0.8 0.7-1 0.9-1.25 1.1-1.6 1.4-2 1.8-2.5 2.2-3.2 2.8-4 3.5-5 4.5-6.3 5.5-8 7.0-10 9.0-12(.5) 11-16 14-20 17-22 (18)20-25 22-32 28-40 |
- - 0.06 0.09 - 0.12 0.18 - 0.25 0.37 0.55 0.75 - 1.1 1.5 - 2.2 3 4 5.5 7.5 - - 11 15 18.5 |
J7MN-12-E16 J7MN-12-E2 J7MN-12-E25 J7MN-12-E32 J7MN-12-E4 J7MN-12-E5 J7MN-12-E63 J7MN-12-E8 J7MN-12-1 J7MN-12-1E25 J7MN-12-E6 J7MN-12-2 J7MN-12-2E5 J7MN-12-3E2 J7MN-12-E4 J7MN-12-E5 J7MN-12-6E3 J7MN-12-8 J7MN-12-10 J7MN-12-12 |
J7MN-25-E16 J7MN-25-E2 J7MN-25-E25 J7MN-25-E32 J7MN-25-E4 J7MN-25-E5 J7MN-25-E63 J7MN-25-E8 J7MN-25-1 J7MN-25-1E25 J7MN-25-E6 J7MN-25-2 J7MN-25-2E5 J7MN-25-3E2 J7MN-25-E4 J7MN-25-E5 J7MN-25-6E3 J7MN-25-8 J7MN-25-10 J7MN-25-12E5 J7MN-25-16 J7MN-25-20 J7MN-25-22 J7MN-25-25 |
J7MN-50-25 J7MN-50-32 J7MN-50-40 |
Характеристики
Type | J7MN-3P | J7MN-3R | J7MN-6R | J7MN-9R | |
---|---|---|---|---|---|
Number of poles | 3 | 3 | 3 | 3 | |
Max. rated current Inmax (= max. rated operational current Ie) |
A | 32 | 32 | 63 | 100 |
Permissible ambient temperature | Storage/transport | -50 to 80°C | |||
Operation | -20 to 60°C | ||||
Rated operational voltage Ue | V | 690 | |||
Rated frequency | Hz | 50/60 | |||
Rated insulation voltage Ui | V | 690 | |||
Rated impulse withstand voltage Uimp | kV | 6 | |||
Utilization category | IEC 60 947-2 (circuit breaker) | A | |||
IEC 60 947-4-1 (motor starter) | AC-3 | ||||
Class | According to IEC 60 947-4-1 | 10 | |||
Degree of protection | According to IEC 60 529 | IP20 | IP20 | IP20 | IP20 |
Phase failure sensitivity | According to IEC 60 947-4-1 | Yes | |||
Explosion protection | According to EC Directive 94191EC | Yes | |||
Isolator characteristics | According to IEC 60 947-3 | Yes | |||
Main and EM. STOP switch characteristics | According to IEC 60 204-1 (VDE113) | Yes | |||
Safe isolation between main and auxiliary circuits According to DIN VDE 0106 Part 101 | Up to 400 V + 10% | Yes | |||
Up to 415 V + 5% | Yes | ||||
Mechanical endurance | Operating cycles | 100,000 | 100,000 | 50,000 | 50,000 |
Electrical endurance | 100,000 | 100,000 | 25,000 | 25,000 | |
Max. operating frequency per hour (motor starts) | 1/h | 25 | 25 | 25 | 25 |